1. What Is CPR in the Cable Industry?
CPR stands for the Construction Products Regulation, a European regulatory framework governing construction products placed on the European market.
For power, control and communication cables intended for permanent installation in buildings and construction works, CPR establishes requirements for declaring their reaction-to-fire performance.
Under EN 50575, cables within its scope are evaluated according to harmonized requirements. Their reaction-to-fire performance is classified in accordance with EN 13501-6.
The European cable classification system includes seven main Euroclasses:
- Aca
- B1ca
- B2ca
- Cca
- Dca
- Eca
- Fca
Among these classifications, B2ca, Cca, Dca and Eca are particularly useful to understand when evaluating fire performance requirements for communication and data cables.
2. What Are the Differences Between B2ca, Cca, Dca and Eca?
The four classifications represent different levels of reaction-to-fire performance. They mainly differ in their requirements for flame spread, heat release and fire growth.
B2ca – Very High Reaction-to-Fire Performance
B2ca is one of the higher reaction-to-fire classifications for cables under CPR.
Cables classified as B2ca must meet demanding requirements for heat release, flame spread and fire growth under the specified testing conditions.
This classification may be required in buildings and infrastructure projects where more stringent fire safety performance is specified.
Cca – High Reaction-to-Fire Performance
Cca represents a high level of reaction-to-fire performance, with requirements for limiting flame spread and heat release.
Compared with B2ca, Cca allows higher heat release and flame spread under the applicable classification criteria.
It is used in projects where Cca-classified cables are specified.
Dca – Intermediate Reaction-to-Fire Performance
Dca represents a lower reaction-to-fire performance level than Cca.
The classification involves assessment of heat release and fire growth under the EN 50399 test conditions, together with the applicable single-cable flame propagation requirements.
It is an option for projects requiring Dca-classified cables.
Eca – Basic Reaction-to-Fire Performance
Eca is a basic reaction-to-fire classification.
Its main assessment is based on the vertical flame propagation test for a single cable according to EN 60332-1-2.
It is suitable only where the applicable building regulations and project specifications permit Eca classification.
Comparison of CPR Cable Euroclasses
| Euroclass | General Performance Level | Main Testing Requirements |
|---|---|---|
| B2ca | Very high | EN 50399 + EN 60332-1-2 |
| Cca | High | EN 50399 + EN 60332-1-2 |
| Dca | Intermediate | EN 50399 + EN 60332-1-2 |
| Eca | Basic | EN 60332-1-2 |
The general reaction-to-fire performance hierarchy is:
B2ca > Cca > Dca > Eca
This comparison refers to the main Euroclass criteria. Actual cable selection should also consider the supplementary classifications and project requirements.
3. What Are the Differences Between B2ca and Cca?
B2ca and Cca are both higher-performance CPR cable classifications and involve more demanding testing than Dca and Eca.
However, their classification limits are different.
Both classes are evaluated using EN 50399 with a 20.5 kW flame source, together with EN 60332-1-2.
The main differences include:
- B2ca has stricter limits for total heat release.
- B2ca has stricter limits for peak heat release rate.
- B2ca has stricter limits for fire growth rate.
- B2ca has a more restrictive flame spread limit.
Therefore, achieving B2ca classification generally requires more demanding material formulation and cable construction optimization than achieving Cca.
For cable manufacturers, selecting a suitable flame-retardant compound is important, but the complete cable structure and manufacturing process also influence the final classification.
4. What Do the Additional CPR Classifications s, d and a Mean?
For B2ca, Cca and Dca cables, the main Euroclass can be accompanied by three additional classifications describing smoke production, flaming droplets and acidity.
These classifications provide further information about cable behaviour during a fire.
Smoke Production – s Classification
The s classification evaluates the amount and rate of smoke generated during cable combustion.
- s1: Low smoke production.
- s2: Medium smoke production.
- s3: Does not meet the s1 or s2 criteria.
The s1 category can be further divided into:
- s1a: Higher light transmittance, at least 80%.
- s1b: Light transmittance of at least 60% but below 80%.
Flaming Droplets – d Classification
The d classification evaluates flaming droplets and particles released during combustion.
- d0: No flaming droplets or particles within the specified test period.
- d1: No flaming droplets or particles persisting longer than 10 seconds within the specified test period.
- d2: Does not meet the d0 or d1 criteria.
Acidity – a Classification
The a classification evaluates the acidity and conductivity of gases released during cable combustion.
- a1: Higher performance, with conductivity below 2.5 μS/mm and pH above 4.3.
- a2: Conductivity below 10 μS/mm and pH above 4.3.
- a3: Does not meet the a1 or a2 criteria.
For example, a cable classified as Cca-s1,d0,a1 meets the Cca main classification and the specified additional requirements for smoke, flaming droplets and acidity.
It is important to note that Eca does not carry these supplementary s, d and a classifications under the CPR cable classification system.
5. Which Testing Standards Are Used for CPR Cable Classification?
Different testing methods are used to evaluate cable reaction-to-fire performance.
EN 50399 – Heat Release and Flame Spread Test
EN 50399 evaluates the fire behaviour of bunched cables exposed to a specified flame source.
It measures parameters such as:
- Flame spread (FS)
- Total heat release (THR)
- Peak heat release rate (HRR)
- Fire growth rate index (FIGRA)
- Smoke production
This test is used for B2ca, Cca and Dca classifications, as well as B1ca under its applicable test conditions.
EN 60332-1-2 – Single Cable Vertical Flame Test
This method evaluates the flame propagation characteristics of a single vertically installed cable exposed to a specified flame.
It is relevant to B2ca, Cca, Dca and Eca classifications.
EN 61034-2 – Smoke Density Test
This method measures smoke density and light transmittance during cable combustion under specified conditions.
It provides additional information relevant to smoke performance classification.
EN 60754-2 – Acidity and Conductivity Test
This method evaluates the acidity and conductivity of gases released during cable combustion.
It is used to determine the supplementary acidity classification.
6. What Is the Relationship Between CPR and LSZH?
CPR and LSZH are closely related in cable material selection, but they represent different concepts.
CPR is a European regulatory framework for construction products, including cables within its scope. It establishes requirements for declaring the reaction-to-fire performance of finished cables.
LSZH stands for Low Smoke Zero Halogen. It describes cable material characteristics related to smoke generation and halogen acid gas emissions during combustion.
LSZH compounds are widely used in communication cables, data cables and other applications where reduced smoke and halogen-free properties are required.
However, using LSZH material does not automatically mean that a finished cable achieves B2ca, Cca, Dca or Eca classification.
The final CPR performance depends on multiple factors:
- Insulation and sheath material formulations.
- Cable construction and dimensions.
- Flame-retardant performance of the complete cable.
- Extrusion and manufacturing conditions.
- Finished-cable fire test results.
Therefore, cable manufacturers should evaluate the complete cable structure rather than relying only on the properties of an individual compound.
7. Is European B1ca the Same as China's B1 Fire Classification?
This is an important distinction for international cable manufacturers.
Although both classifications use the term B1, European CPR B1ca and China's B1 fire classification under GB/T 31247 belong to different classification systems.
They have different testing methods, classification criteria and application frameworks.
European B1ca is part of the CPR cable Euroclass system under EN 13501-6.
China's B1 classification is determined according to GB/T 31247, which addresses the classification and requirements for burning behaviour of
cables and optical cables.
Consequently, a cable meeting China's B1 classification cannot automatically be considered compliant with European B1ca requirements.
Manufacturers exporting cables to Europe should identify the specific CPR Euroclass required by their customers and complete the relevant European testing and classification procedures.
8. How Should Cable Manufacturers Select CPR LSZH Communication Cable Compounds?
When developing communication and data cables for the European market, manufacturers should first identify the required CPR classification based on the installation environment, national regulations and project specifications.
The following factors should be considered:
1. Required CPR Euroclass
Confirm whether the finished cable needs to achieve B2ca, Cca, Dca or Eca classification.
2. Supplementary Fire Performance
Determine whether the project requires additional smoke, flaming droplet and acidity classifications, such as s1,d0,a1.
3. Cable Construction
Consider conductor configuration, insulation materials, sheath thickness and overall cable design.
4. Material Processing
Evaluate extrusion characteristics, processing temperature and compatibility with existing production equipment.
5. Finished-Cable Testing
Confirm that the complete cable meets the required reaction-to-fire performance through the applicable testing and classification procedures.
Choosing an appropriate LSZH compound is an important step in cable development, but finished-cable testing remains essential.
Conclusion
Understanding CPR cable classification helps communication cable manufacturers develop products that meet European fire safety requirements.
B2ca, Cca, Dca and Eca represent different reaction-to-fire performance levels, while supplementary classifications provide additional information about smoke production, flaming droplets and combustion gas acidity.
For communication cable manufacturers looking for thermoplastic LSZH sheathing materials, Opta offers several grades for different CPR-oriented applications:
- EPC6907 – Eca LSZH Communication Cable Compound
- EPC6908 – Dca LSZH Communication Cable Compound
- EPC6910 and EPC6906 – Cca LSZH Communication Cable Compounds
The appropriate material should be selected according to the cable construction, processing conditions and required finished-cable performance.